Current Relay

Home ProductCurrent Relay

30A 60A 415V Current Relay

.Compact Design
.Multiple Protection Functions
.Wide Current Adjustment Range (10:1)
.Ammeter Function
.Trip Indication LED

Product Description

Electronic Overload Relays

Features

.Compact Design

.Multiple Protection Functions

.Wide Current Adjustment Range (10:1)

.Ammeter Function

.Trip Indication LED

.High Accuracy

.Manual Instantaneous Reset

.Electrical Remote Reset

.Test Function

.Ambient Insensitive

.Low Energy Consumption

.Fail-safe Operation (No Volt Release)

Over-Current Protection

Over-current Protection is provided by tripping the relay when motor operating current (In) exceeds over-current setting (Is) of HTHY for a period greater than the preset operating time (0-Time)

image003

O-Twne Settng

Typtcai Trip Time under (Xer-ainertf)

Wide Adjustment Range

HTHY has a wide current adjustment range of over 10:1. It enables three type models to cover a wide range from 0.1 Aup to 600A thus reducing the number and type of relays that must be inventoried for spare purposes.

Looping Option

Some motor size may require only one-third or one-fourth of particular HTHY current ragne. These inatallations can be accommodated by looping the motor wire 2 or 3 times through the integral current transformers of the HTHY. This reduces the number and type of relays inventoried for spare purposes. Each additional loop will increase the currents measured as indicated by the following chart.

1

image005

Straight-through-Wiring Looping Oplk>n (l-Loop)

HTHYSS

image007

.2 Integral Current Transformers

.Electronic Shear-pin Function, Independently Adjustable Starting Trip Delay (D-Time) & Trip Time (O-TIME)

Protection

Protective Item
Operating (Trip) Tinie
Over-cumrent
O-TJME
Phase Loss
O-TIME
Locked Rotor
O-TIME+D-TIME

Specification

Type

Range

Current Setting 05

0.5-6A

30

3-30A

60

5-60A

100-(over 60A)

Ext.CT Option

Time Start D-TIME

0.2-30 sec

Setting Trip O-TIME

0.2-10sec

Control \bltage 220

AC90-250V

(50/60Hz) 440

AC320-480V

Output Relay Mode

l-SPDT (lC)

Rating

AC250V/3 A Resistive

Status

Normally Energized

Time-Current Characteristic

Definite

Operating (Trip) Indication

2-LED

Mount

35mm Din-rail/Panel

Phase Loss Protection

During a phase loss, the motor winding current may increase by 150% or more. As the motor winding current increases, the winding temperature may also increase and possibly damage the winding insulation. The quick trip time on HTHY helps to prevent over-current damage to the windings.

image009

Ammeter Function & Trip Indication

Indication LED on the dial plate provides trip indication and ammeter functions. The LED starts to flash at the point where motor current is equal to current setting level (Is), so user can verify motor current by reading the LOAD adjustment scale on the dial plate. This also provides an accurate current setting. The LED is illuminated when motor current exceeds current setting (Overload Status). After tripping has occurred, the LED stays on until the relay is reset.

The trip indication is also an important feature of a multiple relay & contactor (starter) installation.

External Current Transformer Option

Ordering option-05 type of each model fitted to an external current transformer can achieve higher ampere ranges. (Ext.CT Option)

Type Current Ratio of Ext. CT Current Setting Range

05

0.5-6A

Ext.CT Option

100

100:5

10-120A

200

200:5

20-240A

300

300:5

30-360A

400

400:5

40-480A

500

500:5

50-600A

600

600:5

60-720A

image011

External CT Option

Manual Instantaneous Reset

Pushing RESET button on the dial plate or interrupting power supply provides a manual instantaneous reset.

Electrical remote reset is also provided by the panel-mounted RESET button.

Low Energy Consumption

HTHY-SS uses only 250mA of power, much less than thermal bimetallic overload relays, The result is significant cost savings over the life of relays (over 20 times cost saving).

Typical Wiring

image013

Multi protect function, under current relay, popular in the motor protection. If you are also looking for overcurrent protection relay, current monitoring relay, AC current sensing relay and 3 phase monitoring relay, please choose this one. It can help you solve many problem but very simple design, easy to set and good cost.


Send Inquiry

Copyright © 2023 Yueqing Aukeman Electric Co.,Ltd XML | Sitemaps