Home ProductMotor Protector Relay
Applications
With phase failure, overload, unbalance, stall protection, four optional trip classes. No-load start, protection of any phase loss or overload. NO contact protection.
Model Description
Model Selection Table
|
Model |
Rated working current range |
Applicable motor power |
|
ZHRA1-5 |
1A~5A |
0.55kW~2.2kW |
|
ZHRA1-10 |
2A~10A |
1.1kW~4kW |
|
ZHRA1-30 |
6A~30A |
3 kW~15kW |
|
ZHRA1-80 |
16A~80A |
11kW~37kW |
|
ZHRA1-200 |
40A~200A |
55kW~90kW |
|
ZHRA1-400 |
80A~400A |
45kW~185kW |
Technical Parameters
|
Rated control supply voltage |
AC380V、AC220V 50/60Hz |
|
Current measurement accuracy |
≤2% |
|
Setting accuracy |
≤5% |
|
Number of poles |
3P |
|
Rated insulation voltage |
AC690V |
|
IP Class |
IP20 |
|
Coordination type |
2 |
|
Contact capacity |
Ith:5A;AC-15:Ue/Ie 380V/0.95A 240V/1.5A |
|
Use category |
AC-15 |
|
Electrical Life |
105 |
|
Mechanical life |
106 |
|
Altitude |
≤2000m |
|
Allowable relative humidity |
≤50%(40℃)( NO condensation) |
|
Power consumption |
≤1.5 VA |
|
Installation |
Screw mounting |
Wiring Diagram
Dimensions(mm)