Home ProductMulti-Function 3 Phase Voltage Relay
The Phase Failure Protection Voltage Relay is mainly used for AC 50/60Hz, rated voltage below 460V for various fault detection. It is capable of providing relay protection for over-voltage, under-voltage, phase loss, phase breakage, phase sequence, three-phase voltage unbalance, etc. for three-phase input power. Our products are beautifully light outside, small in size and occupy little space. The Phase Failure Protection Voltage Relay is available in a wide range of voltage ratings.
Features
Compared with similar products in the market, we believe that our Phase Failure Protection Voltage Relay is of better quality and lower price. It features a standard modular construction and din rail mounting. The product uses LEDs to display voltage values, fault status, and parameters. Over-voltage and under-voltage values are adjustable, and the operation time is adjustable for more flexible use. The voltage unbalance rate and operation time are also adjustable, making it easy and convenient to use.
Model Description
Model Selection Table
| Model |
Over-voltage |
Under-voltage |
Unbalance |
Phase sequence |
Phase failure |
|||
|
Setting range |
Delay range |
Setting range |
Delay range |
Setting range |
Delay range |
|||
|
ZHRV2-10 |
1.15 |
2s |
0.85 |
2s |
8% |
2s |
● |
● |
Technical Parameters
| Rated supply voltage |
AC220V、AC230、AC240V、AC380V、AC400V、AC415V |
|
Rated supply frequency |
50Hz/60Hz |
|
Over-voltage threshold range |
(1.05~1030)×Ue |
|
Under-voltage thershold range |
(0.70~0.95) ×Ue |
|
Unbalance threshold range |
5%~15% |
|
Action delay range |
0.1s~10s |
|
Phase failure and phase sequence |
≤1s |
|
Voltage measurement error |
≤1%( Entire setting range) |
|
Delay error |
±10%+0.1s |
|
Knob setting accuracy |
±1% Scale value |
|
Rated insulation voltage |
415V |
|
Contact configuration capacity(A) |
10A |
|
IP Class |
IP20 |
|
Class of pollution |
Ⅲ |
|
Electrical Life |
105 |
|
Mechanical life |
106 |
|
Altitude |
≤2000m |
|
Allowable relative humidity |
≤50%(40℃)( No condensation) |
|
Use category |
AC-15 |
|
Short circuit protector type |
RT36-00 5A |
|
Contact capacity |
Ue/le:240V/1.5A,415V/0.95A |
|
Output type |
1C/O |
|
DIN rail Standard |
(width) 35mm(IEC/EN60715) |
Function diagram
Wiring diagram
Dimensions(mm)