Voltage Current Protector

Home ProductVoltage Current Protector

Single-Phase Self-Resetting Adjustable Overvoltage Protector Undervoltage 40A 63A Relay

Single-Phase Self-Resetting Adjustable Overvoltage Protector Undervoltage Protector. 
Detect overvoltage and undervoltage, automatically recover, and protect your power safety.
It has the characteristics of voltage display, automatic reset, and adjustable overvoltage and undervoltage protection values. It can be installed using DIN rail, which is convenient, fast and simple.

Product Description

Technical Data
Type Effective value Accuracy Explain
Effective voltage range AC80~300V 1% Calibratable,with higher accuracy
Effective current range AC0.1~63.0A 1% Calibratable,with higher accuracy
Frequency range 40~70Hz 1% Calibratable,with higher accuracy
Screen refresh rate >1000Hz

Table update 0.1~1.0S 1% Screen value update
Table algorithm RMS
The urban power grid should use this algorithm
Overvoltage and undervoltage return difference 5V
Fixed 5V hysteresis
Timer range 1~999S 1% User Settings
Action time 0.1~10.0S 1% User Settings
DC effective range DC80~300V 1%
Setup menu
Code Option Set range Default Code Option Set range Default
P1 Power-on delay 1-999 5S P9 Rapid power failure protection ON/OFF ON
P2 Recovery delay 1-999 30S
P10
Automatic reset ON:Self-recovery 
OFF:Manual recovery
ON
P3 Overvoltage 130-300 270V
P4 Overvoltage recovery value 125-295 265V P11 Action/knife mode ON/OFF ON
P5 Undervoltage 80-210 170V P12 Energy saving mode ON/OFF OFF
P6 Undervoltage recovery value 85-215 175V P13 Setup lock password 000-999 112
P7 Overvoltage action delay 0.1-10.0 0.5S
P14
Change password lock 000-999 112
P8 Voltage correction -10%-+10% 0V
Note:When  the  value  ofP13  is  not  112,only  the  parameters  can  be  viewed  and  cannot  be  set.P14wll  only  appear  when  the   P13  valueis  correct.
Other operation
Function Explain
Reset In shutdown mode,press the power key for more than 5S to reset all parameters and startup
Toggle display Display Mode 2:+,-Key Switch
Display Mode 3:+,-Key Switch
Turn on/off Short press the power key for operation
Quickly voltage adjustment In the boot state,click the'+'key quickly
Quickly current adjustment In the boot state,click the'-'key quickly
Setting error When the overvoltage is set beow the undervoltage,the protector will always be in the protection state
Reference of calibration table When correcting the voltage/curent,the adjustment must be made with reference to the multimeter with root mean square(RMS)
Modify the setup lock password Reservation

Functions1.Over-voltage protection
2.Under-voltage protection
3.Over-current protection
4.Automatic reclosing5.Voltage/current display6.Adjustable voltage and current trip

7.Automatic reclosing time


Send Inquiry