Technical Parameters
Rated supply voltage |
Ac220V |
Rated supply frequency |
50/60HZ |
Contact Configuration capacity(A) |
32A、40A、63A、80A Resistive |
Maximum load power |
7kVA(40A)、13 kVA(63A)、17 kVA(80A) |
Over-voltage action value |
36G:265V |
Over-voltage reset value |
36G:257V |
under-voltage action value |
36G:175V |
under-voltage reset value |
36G:180V |
Action delay |
36G:0.1s |
Power on delay |
36G:2s |
Reset delay |
36G:1s |
Voltage measurement error |
≤1% |
Delay error |
±10%+0.1s |
Knob setting accuracy |
±1V |
Rated insulation voltage |
415V |
IP Class |
IP20 |
Class of pollution |
Ⅲ |
Electrical Life |
105 |
Mechanical life |
106 |
Altitude |
≤2000m |
Allowable relative humidity |
≤50%(40 oC)(No condensation) |
DIN rail Standard |
(width)35mm(IEC/EN60715) |
Function diagram
Dimensions(mm) |
Wiring diagram |
|
|
Typical applications
Ordering instructions
Model signifivance:
ZHRV2-36G/40A under over voltage relay,adjustable voltage relay,minmimum voltage relay,24 volt relay and voltage protection relay and so on called for multi voltage protection function range.