60A Digital Motor Protection Relay

This product is a digital comprehensive electric machine protector that uses a micro computer control unit (MCU).

Product Description

HTHY-63 Digital Motor Protection Relay Operation Instruction

Functions

1. Motor control relay is a digital comprehensive electric machine protector that uses a micro computer control unit (MCU).

2. Multiple protection functions such as overcurrent, undercurrent, locked rotor, locking, open phase, reverse phase, three phase unbalance protection.

3. Convenient operating: all the functions can be set by operating keys.

4. Digital display of fault reason and fault current value, facilitating fault handling.

5.The three phase current values can be displayed by operating the display key. Usually, only the max. current value is displayed. The percentage of actual load in the set value is displayed by digital cursor.

6. The inverse time limit characteristic or specified time characteristic can be selected according to actual need.

7. Quite strong anti-interference characteristic

8. Its display part and main body can be installed separately to facilitate the installation and operating on panel.

Electric motor relay Specifications and technical parameters

Current setting

Type

Current setting range

06

0.5 to 6A

60

5 to60A

An electric machine above60Ashall be equipped with a 06 type external mutual inductor.

Operate time characteristic

Inverse time limit/specified time

Protection functions

Over current

Operate according to set time

Phase failure

<3S

Reverse phase

0.1S

Unbalance protection

<5S

Stall

5S

Lock

Within 0.5s

Undercurrent

3s

Ground fault

0.05 to 1s (Optional)

Time setting

Definate time

Delay in startting

0 to 60s

Delay in operating

0 to 30s

Inverse time

0 to 60s

Tolerance

Current

+5%

Time

+5%

Operating power

Voltage

AC440V+20%

Frequency

50 to 60Hz

AUX. contact

5A/250VAC(resistive load)

Insulation resistance

Casing and current

2.0KV common frequency 1 min

Between contacts

1.0KV common frequency 1 minute

Operating environment

Temperature

-25~80℃

Humidity

Relative humidity ≤85%

Mounting type

35mm Din-rail/Panel

Phase voltage balance relay Installation and commissioning
1. Before put into use, the protector shall be tested to see whether it can work normally through pressing the test/reset key. Meanwhile, the protector shall enter into the TEST mode, and the function key and setting key shall be pressed for functional setting of the protector.

2. In the Test mode, upon per time of pressing the function key, the display screen will display the contents from1.CHA to Sto, as shown in the table below. For altering the value of displayed function item, the setting key shall be operated to obtain required value and the function key shall be pressed for switching over to the display of next function item. After functional setting, the setting key shall be pressed in Sto function item for storing all the set values.

Function

Sel

Functions

Note

1.CHA

Inv/dEF

Inverse or definite time characteristics

Default is inverse time characteristics

2.dEF

0~30

Set the O-time(Definite time only)

For O-time setting

3.r.p

OFF/on

Reverse phase protection

Default is OFF

4.Und

OFF/30~70(%)

Undercurrent protection

Default is OFF

5.g-F

OFF/0.05~1.0S

Ground fault protection

Default is OFF

6.Stl

OFF/on

Stall function

Default is OFF

7.Loc

OFF/200~900%

Lock function

Default is OFF

8.Ct

1~120

CT ratio

Default is 1:1

9.P.F

On/oFF

Phase failure

Default is on

Sto

Sto

Store

/

3. The operate time can be set by time setting knob, and current set value will be displayed on the display screen.

Inverse time limit characteristic

1) The inverse time limit characteristic (Inv) shall be selected from the functional item1.CHA, and the operate time shall take 600% of rated current in inverse time limit characteristic as benchmark.

2) The operate time can be set to be 0 to 60s, according to the electric machine&rsquo; s starting time.

3) The cold state characteristic curve shall be referred to when the electric machine is being started, while the thermal state characteristic curve shall be referred to after the electric machine is started and the set time is exceeded.

Three phase voltage monitor Specified time characteristic

1. Specified time characteristic dEF (specified time) shall be selected from functional ite 1.CHA.

2. The time setting knob can be used for setting the electric machine&rsquo; s start delay time.

3. The overload delay time can be set by functional item 2.dEF.

4. The current setting knob can be used for setting the operating current, and the current set value will be displayed on the display screen.

1) Taking the electric machine&rsquo; s rated current as benchmark, normally the operating current shall be set to be 110% to 115%of the electric machine&rsquo; s load current during normal running.

2) The digital electric machine protector can be set in two current setting ranges, i.e. 05(0.5~6) and 60(5~60). When an external CT is used, the CT current transmission value shall be set by the function item 8. Ct, e.g. the 8. Ct function item shall be set to be &ldquo; 20&rdquo; for 100:5 mutual inductors, and then the actual current value will be displayed on the display screen after conversion by the protector. (note: the CT ratio is set to be 10:1 for 60 type protectors at delivery, and it&rsquo; s recommended not to alter it at will.)

3) The load current can be set according to the load factor displayed by cursor (normally the load factor is set to be 90%).

5. The display key can be pressed to obtain the set values of current and time as well as the actual value of three phase load currents.

1) Normally the max. current among the three phase currents is displayed on the display screen.

2) Upon per time of pressing the display key, the actual values of three phase currents, set values of load current and time will be displayed in sequence and in cycles.

3) If the display key is not pressed, the normal display state will be restored 3 to 4 seconds later.

60 amp relay 240v Conformation of fault reason by display screen after drop away

If any drop away, the fault reason will be displayed, flickering at intervals of 0.5s.

Upon per time of pressing the &ldquo; display&rdquo; key, the display screen will display the fault reason, actual 3 phase currents during fault and set value, to facilitate analysis of fault reason of electric machine.

Fault display

Fault

Fault reason

image002

Overcurrent

The actual current exceeds the set value.

image004

Undercurrent

Actual current is smaller than set value of undercurrent.

image006

Open phase

Open phase or inter-phase unbalance over 50%

image008

Ground fault

Current leakage, and leakage current over it set value

image010

Lock

Actual current exceeds the set value of locking current.

image012

Reverse phase

The phase sequence of three phase main loop connected to the protector is inverse.

image014

Stall

Locked rotor of electric machine

2

External dimension and installation dimension